Chapter 4 Parameters|
Revision August 2008, 03VE, SW V2.04 4-123
08-11
08-10
08-12
0Hz
Sleep Function
Frequency command
actual output frequency
sleep time
Wake-up frequency
Sleep frequency
08-13 PID Deviation Level Unit: 0.1
Control
mode
VF VFPG SVC FOCPG
Factory Setting: 10.0
Settings 1.0 to 50.0%
08-14 PID Deviation Time Unit: 0.1
Control
mode
VF VFPG SVC FOCPG
Factory Setting: 5.0
Settings 0.1 to 300.0 sec
08-15 Filter Time for PID Feedback Unit: 0.1
Control
mode
VF VFPG SVC FOCPG
Factory Setting: 5.0
Settings 0.1 to 300.0 sec
08-16 Reserved
08-17 Reserved
08-18 Reserved
08-19 Reserved
08-20 Reserved
08-21 Tension Control Selection
Settings 0 to 4 Factory Setting: 0
Control Mode
Settings
VF VFPG SVC FOCPG TQRPG
0: Disable
1: Closed-loop, speed mode
2: Line speed, speed mode
3: Reserved
4: Open-loop, torque mode
Closed-loop, speed mode