Chapter 5 Troubleshooting|
5-2 Revision August 2008, 03VE, SW V2.04
5.2 Ground Fault
GFF
Ground fault
No
Yes
If output circuit(cable or
motor) of AC motor drive
is grounded?
Remove grounding
Maybe AC motor drive has
malfunction or misoperation
due to noise. Please
contact DELTA.
5.3 Over Voltage (OV)
Over voltage
Ye s
No
Ye s
No
No
No
If voltage is within
specification
Reduce voltage to
be within spec.
If over-voltage is occurred without load
Maybe AC motor drive
has malfunction or
misoperation due to
noise. Please contact
DELTA.
Ye s
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
When OV occurs, check if the
voltage of DC BUS is greater
than protection value
If OV occurs when
sudden acceleration
stops
Increase
deceleration
time
Increase setting time
Increase
acceleration
time
Reduce moment
of inertia
Reduce moment of load inertia
Use brake unit or DC brake
Need to check control method. Please contact DELTA.
Need to considerate to
use brake unit and
DC brake

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta Electronics AC Motor Drive VFD-VE Series and is the answer not in the manual?

Delta Electronics AC Motor Drive VFD-VE Series Specifications

General IconGeneral
BrandDelta Electronics
ModelAC Motor Drive VFD-VE Series
CategoryController
LanguageEnglish

Related product manuals