Chapter 4 Parameters|
Revision August 2008, 03VE, SW V2.04 4-97
Over-Current
Detection Level
06-04
Output Current
Output
Frequency
Over-Current Stall
Prevention during
Operation, output
frequency decrease
over-current stall prevention during operation
Time
06-05 Accel./Decel. Time Selection of Stall Prevention at Constant Speed
Control
mode
VF VFPG SVC
Factory Setting: 0
Settings 0 by current accel/decel. time
1 by the 1
st
accel/decel. time
2 by the 2
nd
accel/decel. time
3 by the 3
rd
accel/decel. time
4 by the 4
th
accel/decel. time
5 by auto accel/decel. time
It is used to set the accel./decel. Time selection when stall prevention occurs at constant
speed.
06-06 Over-torque Detection Selection (OT1)
Control
mode
VF VFPG SVC FOCPG TQRPG
Factory Setting: 0
Settings 0 Over-Torque detection disabled.
1 Over-torque detection during constant speed operation, continue to
operate after detection
2 Over-torque detection during constant speed operation, stop
operation after detection
3 Over-torque detection during operation, continue to operate after
detection
4 Over-torque detection during operation, stop operation after
detection
06-07 Over-torque Detection Level (OT1) Unit: 1
Control
mode
VF VFPG SVC FOCPG TQRPG
Factory Setting: 150