2 Installation
2.5 Connecting the inputs
36 Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com
Figure 30:Application example with easy800 standard DC version
Connect easy-DC inputs EASY806-DC-SWD
Use input terminals I1 to I4 of EASY806-DC-SWD to connect pushbutton
actuators, switches or 3- or 4-wire proximity switches. Given the high
residual current, do not use 2-wire proximity switches.
• Digital input signal voltage range
• I1 to I4
Signal OFF: 0 to 5 V.
Signal ON: 15 to 28.8 V.
• Input current:
• I1 to I4: 3.9 mA at 24 V
Figure 31:Application example with EASY806-DC-SWD
→
Feed the digital inputs from the same 24 V DC power source as
the device.