2 Installation
2.5 Connecting the inputs
36 Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com
Figure 30:Application example with easy800 standard DC version
Connect easy-DC inputs EASY806-DC-SWD
Use input terminals I1 to I4 of EASY806-DC-SWD to connect pushbutton
actuators, switches or 3- or 4-wire proximity switches. Given the high
residual current, do not use 2-wire proximity switches.
Digital input signal voltage range
I1 to I4
Signal OFF: 0 to 5 V.
Signal ON: 15 to 28.8 V.
Input current:
I1 to I4: 3.9 mA at 24 V
Figure 31:Application example with EASY806-DC-SWD
Feed the digital inputs from the same 24 V DC power source as
the device.
L01+
L01-
0 V l1 I2 I7
...V
F1
0 V
l3 I4
l5 I6
...
L02+
AB
L01-
F1
L01+
I1 I3I2 I4
24 V
0 V
POW