NotificationUserName = “xx.xx”
FirmwareUpgrade = 0|1 (0=No, 1=Yes)
Examples #> setSNMP User = “readuser”
Comments
(1)
: Writing enabled according to “snmpVersion” status
(2)
: Writing enabled according to “WriteCommunitySecurityLevel” status
(3)
: Writing enabled according to “UserSecurityLevel” status
(4)
: Writing enabled according to “AdminSecurityLevel” status
(5)
: Don’t forget to set echo off
(6)
: The length has to be 8 characters at least.
6.4.3 Trap receivers
6.4.3.1 “getTrap”
Purpose To read a trap receiver setting
Syntax getTrap N [option1] [option2]...
N = 0|1|2
options :
Name
HostName
TrapPort
TrapSnmpVersion
TrapCommunity
TrapSelectedMibs
Examples #> getTrap HostName Name
Comments
6.4.3.2 “SetTrap”
Purpose To modify a trap receiver setting
Syntax setTrap N [option1] [option2]...
N = 0|1|2
options :
Name = “xx..xx”
HostName = “xx..xx”
TrapPort = xx (Default value: 162) (1..65535)
TrapSnmpVersion = Disabled|V1|V3|V1V3
TrapCommunity = “xx..xx”
TrapSelectedMibs = 0|1|2|3|4|5|6|7
(1)
Examples #> setTrap 0 Name=”My application”
Comments
(1)
: bit0 = 1 : MIB Pulsar enabled
bit1 = 1 : Power MIB enabled