www.eaton.com
Network
Management Card
(Network-MS)
User Manual
Network Management Card
– User Manual 34003991XT_EN/JC
Page
93/143
------------------------------------------------------------------------
NETWORK MANAGEMENT CARD
Network settings - SNMP
------------------------------------------------------------------------
1 : Version (Disabled, V1, V3, V1V3) [V1V3]
2 : SNMP port (Default value: 161) [161]
** About V1 **
3 : Community read-only [publicuser]
4 : SNMP write (0=No, 2=Yes) [2]
5 : Community write [privateuser]
(1)
** About V3 **
6 : Read-only user [readuser]
7 : R/O security (1=No Auth, 2=Auth NoPriv, 3=Auth Priv) [2]
8 : Read-only password [***********]
(2)
9 : Read-Write user [writeuser]
10 : R/W security (1=No Auth, 2=Auth NoPriv, 3=Auth Priv) [2]
11 : Read-Write password [***********]
(3)
12 : Notification user name [notifuser]
0 : Exit
----------------------------------------------------------------------
All items from 3 to 11 are read-write or masqued according to “Version” status.
(1) Read-write or read-only according to “SNMP write” status;
(2) Write-only or hidden according to “R/O security” status; the length has to be 8 characters at least;
(3) Write-only or hidden according to “R/W security” status; the length has to be 8 characters at least.
6.3.5 Trap receivers menu
This menu is used to view or modify the applications receiving traps and to configure trap type.
------------------------------------------------------------------------
NETWORK MANAGEMENT CARD
Trap receiver
------------------------------------------------------------------------
1 : Receiver 1
2 : Receiver 2
3 : Receiver 3
0 : Exit
------------------------------------------------------------------------