Menu structure of CI 3000
99
Version 2.09 09. April 2014
S Screens 6-3-2 to 6-3-4 temperature archive
The temperature archives from UA 30/Dixell controllers, AHT controllers and Danfloss controllers
can be selected via the 3 screens 6-3-2 to 6-3-4.
As the case selection and the associated display of the temperature archive is identical for all these
controllers, the instructions are provided using the example of the ”UA30/Dixell” temperature ar
chive.
Page 1 - Selection of the desired case controller (i.e. case)
TEMP-ARCHIV Nr.nnn
Node name ↑ Name of the controller
Position XXXXX → Position of controller, continue to page 2:
- HACCP temperature archive of the selected controller -
Case no. aaa/bbb ↓ Case No.:
aaa current case
bbb max. No. of cases for this LDS component
Using the cursor buttons (↑) (↓) it is possible to scroll from controller (i.e. case) to controller (i.e. case).
The MODE button combined with a cursor button (↑) (↓) springs to the start, i.e. end of the list. This
list contains entries on all available controllers.
Page 2 - HACCP temperature archive (hourly averages) of the selected controller (i.e. case)
TEMP-ARCHIVE DIXELL
P: XXXXX M: aaa ↑ Position and case number of the LDS component
dd.mm.yy 00-03 h ←
04-07 h
08-11 h
12-15 h
16-19 h
20-23 h
Date and time period (4 hours) of the temperature values
--- -22 -D- -27 ↓ 4 temperature values as hourly averages for the time period shown in line 3
--- no valid value available
-D- Defrost
4 hourly averages are always shown per screen. No averages are available for periods less than an hour. With
the cursor buttons (↑) (↓) it is possible to scroll chronologically through the archived values. This switches to the
next/previous set of 4 temperature values. The list contains figures for 31 days.
Praxis tip: The MODE button combined with a cursor button (↑) (↓) springs to the start, i.e. end of
the list.