Alarms and Messages of CI 3000
118
Version 2.09 09. April 2014
No. Messages Cause Correction
Modem faults
85 Modem Fault Modem not recognized, not switched on or not
connected.
Check modem and connection to
CI 3000 Store Computer
86 Error Recipient (n)
n = 0..7
Store Computer cannot transmit alarms to spe
cified remote station. Typical cause: Remote
station busy or modem does not recognize dial
tone. The following alarm destinations are pos
sible:
0 Service Center
1 Fault Service
2 LDSWin Internal 1
3 Voice Message
4 LDSWin Extern 1
5 LDSWin Extern 2
6 SMS
7 FAX
Up to version 4.28:
Check phone number and remote
station
Assignment only applies up to ver
sion 4.28! Due to the new priority
concept no fixed assignment applies
from version <= 5.0!
87 Direct link Modem link temporarily replaced by direct con
nection between LDSWin PC and CI 3000
Store computer (e.g. for local configuring of
LDS System by service technician).
-
Alarm- and special inputs
90 xxxxxxxxxxxxxxxxx Internal message or alarm input
e.g. Input: Int.I/1
(first input on-board).
Correct external alarm fault
91 xxxxxxxxxxxxxxxxx Message or alarm input on SIOX
e.g. Input: SIOX2/5
(2nd SIOX module / channel 5).
Correct external alarm fault
93 Emerg. Generator Emergency power special output activated. -
94 Sprinkler Alarm Sprinkler alarm special output activated. -
95 Store lighting Store lighting special output activated. -
96 Shunt lock Shunt lock special output activated. -
97 Meter control Meter limit exceeded. -
98 Load Rejection Load shedding initiated. -
99
Archives delete Archives deleted. -
Messages delete Message log deleted. -