Alarms and Messages of CI 3000
117
Version 2.09 09. April 2014
No. Messages Cause Correction
Monitoring
52 Controll.Fail. xxx
or
Controll.Fail. Mxx
No response by LDS-component to Store Com
puter requests.
Check power supply and LDS com
ponent connection to CAN bus, i.e.
Modbus.
53 Failure AHT xxx No response by AHT component.
Possible causes:
- Controller failure
- AHT gateway failure
- Failure of link between AHT gateway and
CI 3000 Store computer
Check power supply and connec
tions on AHT components.
Communication
60 Call nnnnnnnn Call to Store Computer from PC. nnnnnnnnnn
is number of LDSWin dongle. Remote PC
phone number is shown as station name.
-
Archive faults
81 Archive Fault nn Archive management error detected on restart. Please contact Service Organization
82 Archive Error nn During operation an error occurred in the archi
ving (error number nn only for internal use)
1. All archives must be saved using
LDSWin (see chapter 6.10.1)
2. Following this, a reorganisation is
to be carried out using the key com
bination MODE + ESC + 6
In the event of uncertainty please
contact the Service Organization
83 Insuff. Memory Archive could not be created for new compo
nent.
Please contact Service Organization
84 Insuff. Memory EU EU archive could not be created for new com
ponent.
Please contact Service Organization