Appendix WinAQMS Mini DAS User manual 1.0
82
6: Test the GSM reception strength. In general any value for the first number
above 10 is good reception and any value other than 99 is good for the second
value.
7: Reboot the logger.
If you are having trouble getting the modem to recognise the dial tone then
use the initialisation string
x3
which will tell the modem to not wait for a valid dial tone before dialling.
Setting up the Siemens M20 modem driver in Windows
2000/XP
Open the Control Panel ->Phone and Modem Options
go to the modems tab -> Add Don't detect the modem. Select it from the list
-> Next
Choose the Siemens M20 GSM -> Next
Select COM X (where X is the serial port the modem is connected to) -> Finish
Setting up the Falcom A2D modem driver in Windows 2000
Open the Control Panel->Phone and Modem Options
go to the modems tab -> Add Don't detect the modem. Select it from the list
-> Next
Choose the Standard 9600 bps modem -> Next
Select COM X (where X is the serial port the modem is connected to) -> Finish
Set up Windows 2000 to Accept Incoming Connections
Open the Control Panel->Network and Dialup Connections->Make new connection-
>Next->Accept Incoming Connections->Next->Chose Standard 9600 bps Modem -
>Next
Do not allow virtual private connections
Select the administrator and the WinAQMS Mini DAS user to be given access to
dialup remotely->Next
Highlight Internet Protocol (TCP/IP)->Properties
Allow callers to access my Local Area Network
Specify IP addresses from 192.168.0.1 to 192.168.0.10->OK->Next->Finish.
Set up Windows XP to Accept Incoming Connections
Open the Control Panel->Network Connections->Create a new connection->Next-
>Accept Incoming Connections->Next->Chose Standard 9600 bps Modem ->Next
Do not allow virtual private connections
Select the administrator and the WinAQMS Mini DAS user to be given access to
dialup remotely->Next
Highlight Internet Protocol (TCP/IP)->Properties
Allow callers to access my Local Area Network
Specify IP addresses from 192.168.0.1 to 192.168.0.10->OK->Next->Finish.
Note: Incoming connections in windows will not re-establish its connection with a modem that
has been switched off unless the logger is rebooted or the modem was disassociated with
incoming connections before it was turned off. IE if the modem loses power and the logger does
not then the logger will no longer listen for incoming connections to the modem.

Table of Contents