EasyManua.ls Logo

Emerson Commander SX - 7.4 - Factory Settings According to the Rating

Emerson Commander SX
140 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
60
ADVANCED USER GUIDE
Commander SX
IP66/Nema 4X variable speed drive
MENU 5: MOTOR CONTROL
CONTROL TECHNIQUES
3854 en - 03.2008 / b
7.4 - Factory settings according to the
rating
Factory settings 5.07 and 5.08 vary according to the drive
rating.
• Factory setting 50 Hz (Eur)
• Factory setting 60 Hz
Note: Factory settings 21.07 and 21.08 are identical to
those for 5.07 and 5.08.
Rating 5.07 5.08
SX13200037 17 1400
SX13200055 27 1429
SX13200075 34 1428
SX23200110 42 1436
SX23200150 60 1437
SX23200220 80 1438
SX33200300 108 1447
SX33200400 138 1451
Rating 5.07 5.08
SX13400075 20 1400
SX13400110 25 1429
SX13400150 35 1428
SX23400220 51 1436
SX23400300 72 1437
SX23400400 91 1438
SX33400550 119 1447
SX33400750 152 1451
Rating 5.07 5.08
SX13200037 18 1680
SX13200055 29 1715
SX13200075 39 1714
SX23200110 56 1723
SX23200150 74 1724
SX23200220 100 1726
SX33200300 135 1736
SX33200400 167 1741
Rating 5.07 5.08
SX13400075 18 1680
SX13400110 26 1715
SX13400150 34 1714
SX23400220 48 1723
SX23400300 62 1724
SX23400400 76 1726
SX33400550 110 1736
SX33400750 140 1741