Menu 10
Unidrive SP Advanced User Guide 193
Issue Number: 10 www.controltechniques.com
SLX.Er Solutions Module slot X trip: Solutions Module in slot X has detected a fault
202,207,212
SLM module category
Check value in Pr 15/16/17.50. The following table lists the possible error codes for the SM-SLM. See the Diagnostics section in the
SM-SLM User Guide for more information.
SLX.HF Solutions Module slot X trip: Solutions Module X hardware fault
200,205,210
Ensure Solutions Module is installed correctly
Return Solutions Module to supplier
SLX.nF Solutions Module slot X trip: Solutions Module has been removed
203,208,213
Ensure Solutions Module is installed correctly
Reinstall Solutions Module
Save parameters and reset drive
SL.rtd Solutions Module trip: Drive mode has changed and Solutions Module parameter routing is now incorrect
215
Press reset.
If the trip persists, contact the supplier of the drive.
SLX.tO Solutions Module slot X trip: Solutions Module watchdog timeout
201,206,211
Press reset.
If the trip persists, contact the supplier of the drive.
t038 User defined trip
38 Onboard PLC and/or SM-Applications program must be interrogated to find the cause of this trip
t040 to t089 User defined trip
40 to 89 Onboard PLC and/or SM-Applications program must be interrogated to find the cause of this trip
t099 User defined trip
99 Onboard PLC and/or SM-Applications program must be interrogated to find the cause of this trip
t101 User defined trip
101 Onboard PLC and/or SM-Applications program must be interrogated to find the cause of this trip
t112 to t160 User defined trip
112 to 160 Onboard PLC and/or SM-Applications program must be interrogated to find the cause of this trip
t168 to t174 User defined trip
168 to 174 Onboard PLC and/or SM-Applications program must be interrogated to find the cause of this trip
Trip Diagnosis
Error Code Trip Description
0 No fault detected
1 Power supply overloaded
2 SLM version is too low
3 DriveLink error
4 Incorrect switching frequency selected
5 Feedback source selection incorrect
6 Encoder error
7 Motor object number of instances error
8 Motor object list version error
9 Performance object number of instances error
10 Parameter channel error
11 Drive operating mode incompatible
12 Error writing to the SLM EEPROM
13 Motor object type incorrect
14 Unidrive SP object error
15 Encoder object CRC error
16 Motor object CRC error
17 Performance object CRC error
18 Unidrive SP object CRC error
19 Sequencer timeout
74 Solutions module over temperature

Table of Contents

Related product manuals