Parameter
structure
Keypad and
display
Parameter
x.00
Parameter
description format
Advanced parameter
descriptions
Macros
Serial communications
protocol
Electronic
nameplate
Performance
Rotor Flux Control
(RFC) mode
8 Unidrive SP Advanced User Guide
www.controltechniques.com Issue Number: 10
0.29
SMARTCARD parameter
data
{11.36} 0 to 999 0 RO Uni NC PT US
0.30 Parameter copying {11.42} nonE (0), rEAd (1), Prog (2), AutO (3), boot (4) nonE (0) RW Txt NC *
0.31 Drive rated voltage {11.33} 200 (0), 400 (1), 575 (2), 690 (3) V
RO Txt NC PT
0.32 Drive rated current {11.32} 0.00 to 9999.99A
RO Uni NC PT
0.33
OL> Catch a spinning motor {6.09} 0 to 3
0 RW Uni US
VT> Rated rpm autotune {5.16}
0 to 2 0 RW Uni US
0.34 User security code {11.30}0 to 999 0 RWUniNCPTPS
0.35 Serial comms mode {11.24} AnSI (0), rtu (1), Lcd (2) rtU (1) RW Txt US
0.36 Serial comms baud rate {11.25}
300 (0), 600 (1), 1200 (2), 2400 (3), 4800 (4),
9600 (5), 19200 (6), 38400 (7),
57600 (8) Modbus RTU only,
115200 (9) Modbus RTU only
19200 (6) RW Txt US
0.37 Serial comms address {11.23}0 to 247 1 RWUniUS
0.38 Current loop P gain {4.13} 0 to 30,000
All voltage
ratings: 20
200V drive: 75
400V drive: 150
575V drive: 180
690V drive: 215
RW Uni US
0.39 Current loop I gain {4.14}
0 to 30,000 All voltage
ratings 40
200V drive: 1000
400V drive: 2000
575V drive: 2400
690V drive: 3000
RW Uni US
0.40 Autotune {5.12} 0 to 2 0 to 4 0 to 6 0 RW Uni
0.41
Maximum switching
frequency
{5.18} 3 (0), 4 (1), 6 (2), 8 (3), 12 (4), 16 (5) kHz 3 (0) 6 (2) RW Txt RA US
0.42 No. of motor poles {5.11} 0 to 60 (Auto to 120 pole) 0 (Auto) 6 POLE (3) RW Txt US
0.43
OL & VT> Motor rated
power factor
{5.10} 0.000 to 1.000
0.850 RW Uni US
SV> Encoder phase angle {3.25}
0.0 to 359.9° 0.0 RW Uni US
0.44 Motor rated voltage {5.09} 0 to AC_voltage_set_max V
200V drive: 230
400V drive: EUR> 400, USA> 460
575V drive: 575
690V drive: 690
RW Uni RA US
0.45
OL & VT> Motor rated full
load speed (rpm)
{5.08}
0 to 180,000
rpm
0.00 to
40,000.00
rpm
EUR> 1,500
USA> 1,800
EUR>
1,450.00
USA>
1,770.00
RW Uni US
SV> Motor thermal time
constant
{4.15}
0.0 to 3000.0 20.0 RW Uni US
0.46 Motor rated current {5.07} 0 to Rated_current_max A Drive rated current [11.32] RW Uni RA US
0.47 Rated frequency {5.06}
0 to 3,000.0
Hz
0 to 1,250.0
Hz
EUR> 50.0
USA> 60.0
RW Uni US
0.48 Operating mode selector {11.31}
OPEn LP (1), CL VECt (2),
SErVO (3), rEgEn (4)
OPEn LP (1) CL VECt (2) SErVO (3) RW Txt NC PT
0.49 Security status {11.44} L1 (0), L2 (1), Loc (2)
RW Txt PT US
0.50 Software version {11.29} 1.00 to 99.99
RO Uni NC PT
* Modes 1 and 2 are not user saved, Modes 0, 3 and 4 are user saved
Parameter
Range(
Ú) Default(Ö)
Type
OL VT SV OL VT SV
Coding Attribute
OL Open loop
CL Closed loop vector and Servo
VT Closed loop vector
SV Servo
{X.XX} Copied advanced parameter
RW Read/write: can be written by the user
RO Read only: can only be read by the user
Bit 1 bit parameter: ‘On’ or ‘OFF’ on the display
Bi Bipolar parameter
Uni Unipolar parameter
Txt Text: the parameter uses text strings instead of numbers.
FI
Filtered: some parameters which can have rapidly changing
values are filtered when displayed on the drive keypad for
easy viewing.
DE
Destination: This parameter selects the destination of an
input or logic function.
RA
Rating dependent: this parameter is likely to have different
values and ranges with drives of different voltage and
current ratings. Parameters with this attribute will not be
transferred to the destination drive by SMARTCARDs when
the rating of the destination drive is different from the
source drive and the file is a parameter file. However, with
software V01.09.00 and later the value will be transferred if
only the current rating is different and the file is a
differences from default type file.
NC
Not copied: not transferred to or from SMARTCARDs
during copying.
PT Protected: cannot be used as a destination.
US
User save: parameter saved in drive EEPROM when the
user initiates a parameter save.
PS
Power-down save: parameter automatically saved in drive
EEPROM when the under volts (UV) trip occurs. With
software version V01.08.00 and later, power-down save
parameters are also saved in the drive when the user
initiates a parameter save.
Coding Attribute

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson unidrive sp and is the answer not in the manual?

Emerson unidrive sp Specifications

General IconGeneral
TypeAC Drive
Storage Temperature-40°C to +70°C
Communication OptionsCANopen, Ethernet, Profibus, DeviceNet
Safety FeaturesSafe Torque Off (STO), Safe Stop 1 (SS1), Safe Operating Stop (SOS)
Overload150% for 60 seconds
EnclosureIP20
Output Voltage Range0 - Input Voltage
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short Circuit
Humidity95% non-condensing
Cooling MethodFan cooled
DimensionsVaries depending on the power rating and enclosure type
WeightVaries depending on the power rating and enclosure type
Input Voltage200 VAC - 690 VAC ±10%

Related product manuals