15 – 2
Section 15 Compressor Scheduling
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.3
Time
This setpoint allows selection of Hours, Minutes and
AM/PM values for an event. When time set for an event
is achieved, control mode will get changed as selected
for that event.
The range of values allowed to set for Hours setpoint is
1 – 12 for 12-hour format and 0 – 23 for 24 hour format.
The range of values allowed to set for Minutes setpoint is
0 – 59. AM/PM selection is active for selection only when
Time Format selected in conguration screen is 12 hour.
When the scheduling feature is enabled and No. of con-
trollers for Suction Pressure Control & Process Control
are changed in conguration screen (which makes con-
trol modes selected in com- pressor scheduling screen
invalid), then the feature will get disabled automatically
and indication will be sent to operator to correct the
setting.