19 – 12
Section 19 • Compressor Sequencing
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.3
7. Set the Communications Active Remote Control to
“ETHERNET” for each compressor.
8. Apply these settings before exiting the Conguration
screen.
9. Enable the compressor sequencing.
10. Assign a Network Name for sequencing.
11. Apply these settings and exit the screen.
NOTE
Ethernet settings should be set before setting
compressor sequencing settings in the conguration
screen. Available devices in the same network
would be automatically added to compressors
device list when sequencing option is enabled from
conguration screen.
At this point the compressor will begin multicasting its
status information over the network at a rate of every 20
seconds. (After all the Compressor is congured, the in-
formation will be populated in the Sequencing menu of
the all Compressor). Exit out of the conguration screen
and then put other compressors in Auto Seq Stand-By
mode by pressing Start->Seq Stand-By, see Figure 19-11.
After Pressing the Seq Stand-By button, the main win-
dow top status bar will display run mode as “Seq Stand-
by” and “Auto Seq Stand-by” message on top banner, see
Figure 19-12. When other compressors are placed in seq
standby then press start->Auto Seq button to start com-
pressor sequencing. When Compressor gets chance to
run based on the set priority, the main window top sta-
tus bar will display run mode as “Auto Seq”, see Figure
19-13. The compressor can get out from sequencing
by pressing Stop button from Main Screen. Compressor
can again be part of sequencing network by selection of
Auto Seq or Seq Stand-by option, see Figure 19-11.
Figure 19-11. Compressor Start Dialog – Auto Seq and Seq Stand-By