EasyManua.ls Logo

Emerson Vilter MicroVission - Page 205

Emerson Vilter MicroVission
262 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
B − 1
Appendix B Communication Tables
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.3
Table B-1. Digital Inputs Block
MicroVission Communication Table
Scope: MicroVission Programs – version 1.1
NOTES:
All ENUM variables are of INT (Integer) type
All F-INT data types represent oating point values
as INT types multiplied by 10
All Pressures are in Psig
All Temperatures are in Fahrenheit
Modbus TCP addressing is PLC-style (Base 1) ad-
dressing
On Error, Modbus TCP server only returns an error
code of “Illegal Data Address”
Ethernet IP
Address
Modbus
Address
Digital Inputs Data Type Value Mode
Lower
Range
Higher
Range
N50:0 40001 Setpoint 1/2 INT 0 = OFF, 1 = ON Read NA NA
N50:1 40002 Remote Decrease INT 0 = OFF, 1 = ON Read NA NA
N50:2 40003 Remote Increase INT 0 = OFF, 1 = ON Read NA NA
N50:3 40004 Remote Start/Stop INT 0 = OFF, 1 = ON Read NA NA
N50:4 40005 Low Oil Level INT 0 = OFF, 1 = ON Read NA NA
N50:5 40006 High Level Shutdown INT 0 = OFF, 1 = ON Read NA NA
N50:6 40007 Compressor Auxiliary INT 0 = OFF, 1 = ON Read NA NA
N50:7 40008 Auxiliary 1 INT 0 = OFF, 1 = ON Read NA NA
N50:8 40009 Auxiliary 2 INT 0 = OFF, 1 = ON Read NA NA
N50:9 40010 Auxiliary 3 INT 0 = OFF, 1 = ON Read NA NA
N50:10 40011 Auxiliary 4 INT 0 = OFF, 1 = ON Read NA NA
Table B-2. Digital Outputs Block
Ethernet IP
Address
Modbus
Address
Digital Outputs Data Type Value Mode
Lower
Range
Higher
Range
N51:0 40030 Oil Return Solenoid INT 0 = OFF, 1 = ON Read NA NA
N51:1 40031 Unloader #4 INT 0 = OFF, 1 = ON Read NA NA
N51:2 40032 Unloader #3 INT 0 = OFF, 1 = ON Read NA NA
N51:3 40033 Unloader #2 INT 0 = OFF, 1 = ON Read NA NA
N51:4 40034 Unloader #1 INT 0 = OFF, 1 = ON Read NA NA
N51:5 40035 Trip INT
0 = OFF, 1 = ON
(ON when no Trip)
Read NA NA
N51:6 40036 Oil Crank Case Heater INT 0 = OFF, 1 = ON Read NA NA
N51:7 40037 Compressor Start INT 0 = OFF, 1 = ON Read NA NA
N51:8 40038 Remote Ready INT 0 = OFF, 1 = ON Read NA NA
N51:9 40039 Auxiliary Output#1 INT 0 = OFF, 1 = ON Read NA NA
N51:10 40040 Auxiliary Output#2 INT 0 = OFF, 1 = ON Read NA NA
N51:11 40041 Auxiliary Output#3 INT 0 = OFF, 1 = ON Read NA NA
N51:12 40042 Auxiliary Output#4 INT 0 = OFF, 1 = ON Read NA NA
All registers returned (INT and F-INT) are 2 bytes
long
For Ethernet/IP, use INT data type and PLC-5 Word
Range Read/Write MSG instructions
Remote commands cannot be issued if the panel is
in the “Remote Lock” mode
Polling rates should not be less than 5 secs
Writes to the MicroVission should only occur when
a value needs to be changed
Lower Range and Higher Range values mentioned
are default values of MicroVission setpoints
Users can modify Lower Range & Higher Range
values from MicroVission Panel and accordingly
maintain their own table

Table of Contents

Other manuals for Emerson Vilter MicroVission

Related product manuals