B − 12
Appendix B • Communication Tables
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.3
Table B-18. Alarms/Trips Block (Page 1) (1 of 2)
Ethernet IP
Address
Modbus
Address
Alarms/Trips (Page 1) Data Type Value Mode
Lower
Range
Higher
Range
N65:0 40400 Low Suction Pressure Alarm Setpoint #1 F-INT
Read-
Write
-15 300
N65:1 40401 Low Suction Pressure Trip Setpoint #1 F-INT
Read-
Write
-15 300
N65:2 40402 High Discharge Pressure Alarm Setpoint #1 F-INT Read
N65:3 40403 High Discharge Pressure Trip Setpoint #1 F-INT Read
N65:4 40404 Low Process Temperature Alarm Setpoint #1 F-INT
Read-
Write
-100 210
N65:5 40405 Low Process Temperature Trip Setpoint #1 F-INT
Read-
Write
-100 210
N65:6 40406
High Process Temperature Alarm Setpoint
#1
F-INT
Read-
Write
-100 210
N65:7 40407 Low Suction Pressure Alarm Setpoint #2 F-INT
Read-
Write
-15 300
N65:8 40408 Low Suction Pressure Trip Setpoint #2 F-INT
Read-
Write
-15 300
N65:9 40409 High Discharge Pressure Alarm Setpoint #2 F-INT Read
N65:10 40410 High Discharge Pressure Trip Setpoint #2 F-INT Read
N65:11 40411 Low Process Temperature Alarm Setpoint #2 F-INT
Read-
Write
-100 210
Table B-17. Pulldown Block
Ethernet
IP Address
Modbus
Address
Pulldown
Data
Type
Value Mode
Lower
Range
Higher
Range
N63:0 40290
Step Value (Suct. Press/
Proc Temp)
F-INT Read-Write 0.0 10.0
N63:1 40291
Delay Per Step Hours
(Suct. Press/Proc Temp)
INT Read-Write 0 20
N63:2 40292
Delay Per Step Minutes
(Suct. Press/Proc Temp)
INT Read-Write 0 59
N63:3 40293
Stop Value (Suct. Press/
Proc Temp)
F-INT Read-Write -15.0 200.0
N63:4 40294
Auto Cycle Differential
Start Offset (Suct. Press/
Proc Temp)
F-INT Read-Write 1.0 20.0
N63:5 40295
Auto Cycle Differential
Stop Offset (Suct. Press/
Proc Temp)
F-INT Read-Write 1.0 20.0
N63:6 40296
Initiate Pulldown at Next
Start / Every Start
INT
1 = Initiate Pulldown
at Next Start,
2 = Initiate Pulldown
at Every Start
Read-Write