B − 17
Appendix B Communication Tables
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.3
Ethernet
IP Address
Modbus
Address
Conguration (Other) Data Type Value Mode
Lower
Range
Higher
Range
N71:7 40617
Discharge Pressure
Control Available
INT 0 = No, 1 = Yes Read NA NA
N71:8 40618
Discharge Pressure Con-
trol # of Setpoints
INT 0 = No, 1 = Yes Read NA NA
N71:9 40619 Restart On Power Failure ENUM
0 = Always
1 = Never
2 = Timed
3 = Remote Lock Off
4 = Boot in Remote (Direct I/O)
Read-
Write
NA NA
N71:10 40620 Oil Monitoring ENUM
0 = No Oil Filter Monitoring
Read NA NA1 = Only Oil Filter In
2 = Oil Filter In and Oil Filter Out
N71:11 40621 Oil Level Trip Available INT 0 = No, 1 = Yes Read NA NA
N71:12 40622 Anti-Recycle ENUM
0 = True Anti-Recycle
Read NA NA1 = Accumulative Anti-Recycle
2 = Hot Starts
N71:13 40623 Compressor Sequencing INT 0 = No, 1 = Yes Read NA NA
N71:14 40624 Idle Time Trip INT 0 = No, 1 = Yes Read NA NA
N71:15 40625
On Communication
Failure
ENUM
0 = Revert to Local Control
Read NA NA
1 = Stop with Alarm
N71:16 40626 Panel ID INT Read NA NA
N71:17 40627 Compressor VFD INT
0 = Disable
1 = Enable
Read NA NA
N71:18 40628
Condenser Control
Enabled
INT
0 = Disable
1 = Enable
Read NA NA
Table B-24. Conguration (Other) Block (continued) (2 of 2)
Table B-25. Trend Chart (1 of 3)
Ethernet
IP Address
Modbus
Address
Trend Chart Data Type Value Mode
Lower
Range
Higher
Range
N72:0 40650 Trend Files Location ENUM
0 = Hard Disk
1 = USB Drive
Read NA NA
N72:1 40651 Motor Current Enabled INT
0 = Disabled
1 = Enabled
Read NA NA
N72:2 40652 Suction Pressure Enabled INT
0 = Disabled
1 = Enabled
Read NA NA
N72:3 40653 Discharge Pressure Enabled INT
0 = Disabled
1 = Enabled
Read NA NA
N72:4 40654 Oil Pressure Enabled INT
0 = Disabled
1 = Enabled
Read NA NA
N72:5 40655 Filter In Pressure Enabled INT
0 = Disabled
1 = Enabled
Read NA NA