B − 25
Appendix B Communication Tables
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.3
NOTE
Compressor Scheduling Enable/Disable: if a valid schedule has not been dened (on screen or through com-
munications), this command will fail.
Compressor Scheduling Control Mode ENUM values:
0 = Unscheduled
1 = Suction Pressure SP1
2 = Suction Pressure SP2
3 = Process Control SP1
4 = Process Control SP2
5 = Discharge Pressure SP1
6 = Discharge Pressure SP2
If the control mode being set isn’t active in the conguration, the command will result in error. This value can be
changed only when the schedule is disabled
Compressor Scheduling Hour INT – This value can be changed only when the schedule is disabled
Compressor Scheduling Minute INT – This value can be changed only when the schedule is disabled