Commissioning Proline Prowirl F 200 PROFIBUS PA
106 Endress+Hauser
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
entry
Factory setting
Operating mode – Define the output as a pulse,
frequency or switch output.
• Pulse
• Frequency
• Switch
Pulse
Assign pulse output The Pulse option is selected in
the Operating mode
parameter.
Select process variable for
pulse output.
• Off
• Volume flow
• Corrected volume
flow
• Mass flow
• Total mass flow
*
• Energy flow
*
• Heat flow
difference
*
Volume flow
Mass unit – Select mass unit. Unit choose list Country-specific:
• kg
• lb
Volume unit – Select volume unit. Unit choose list Country-specific:
• m³
• ft³
Corrected volume unit – Select corrected volume unit. Unit choose list Country-specific:
• Nm³
• Sft³
Energy unit For the following order code:
"Sensor version", option "Mass
flow"
Select energy unit. Unit choose list Country-specific:
• kWh
• Btu
Value per pulse The Pulse option is selected in
the Operating mode
parameter, and one of the
following options is selected in
the Assign pulse output
parameter (→ 106):
• Volume flow
• Corrected volume flow
• Mass flow
• Total mass flow
*
• Energy flow
*
• Heat flow difference
*
Enter measured value at which
a pulse is output.
Positive floating-
point number
Depends on country
and nominal
diameter
Pulse width In the Operating mode
parameter, the Pulse option is
selected and one of the
following options is selected in
the Assign pulse output
parameter (→ 106):
• Volume flow
• Corrected volume flow
• Mass flow
• Total mass flow
*
• Energy flow
*
• Heat flow difference
*
Define time width of the
output pulse.
5 to 2 000 ms 100 ms