Proline Prowirl F 200 PROFIBUS PA Operation
Endress+Hauser 129
Parameter Prerequisite Description User interface
Temperature Displays the temperature currently
measured.
Dependency
The unit is taken from the
Temperature unit parameter
Signed floating-point
number
Calculated saturated steam pressure The following conditions are met:
Order code for "Sensor version",
option "Mass flow"
The Steam option is selected in the
Select medium parameter.
Displays the saturated steam pressure
currently calculated.
Dependency
The unit is taken from the Pressure
unit parameter
Signed floating-point
number
Steam quality The following conditions are met:
Order code for "Sensor version",
option "Mass flow"
The Steam option is selected in the
Select medium parameter.
Displays the current steam quality.
Depends on the compensation mode of
the steam quality (Steam quality
parameter (7605)).
Signed floating-point
number
Total mass flow The following conditions are met:
Order code for "Application package",
option EU "Wet steam measurement"
The Steam option is selected in the
Select medium parameter.
Displays the total mass flow currently
calculated (steam and condensate).
Dependency
The unit is taken from the Mass flow
unit parameter
Signed floating-point
number
Condensate mass flow The following conditions are met:
Order code for "Application package",
option EU "Wet steam measurement"
The Steam option is selected in the
Select medium parameter.
Displays the condensate mass flow
currently calculated.
Dependency
The unit is taken from the Mass flow
unit parameter
Signed floating-point
number
Energy flow For the following order code:
"Sensor version", option "Mass flow"
Displays the energy flow currently
calculated.
Dependency
The unit is taken from the Energy flow
unit parameter
Signed floating-point
number
Heat flow difference The following conditions are met:
Order code for "Sensor version", option
"Mass flow"
In the Select gas type parameter, one
of the following options is selected:
Single gas
Gas mixture
Natural gas
User-specific gas
Displays the heat flow difference
currently calculated.
Dependency
The unit is taken from the Energy flow
unit parameter
Signed floating-point
number
Reynolds number For the following order code:
"Sensor version", option "Mass flow"
Displays the Reynolds number currently
calculated.
Signed floating-point
number
Density For the following order code:
"Sensor version", option "Mass flow"
Displays the density currently
measured.
Dependency
The unit is taken from the Density unit
parameter
Positive floating-point
number
Specific volume For the following order code:
"Sensor version", option "Mass flow"
Displays the current value for the
specific volume.
Dependency
The unit is taken from the Specific
volume unit parameter
Positive floating-point
number
Pressure For the following order code:
"Sensor version", option "Mass flow"
In the External value parameter, the
Pressure option is selected.
Displays the current process pressure.
Dependency
The unit is taken from the Pressure
unit parameter
0 to 250 bar