Proline Prowirl F 200 PROFIBUS PA Diagnostics and troubleshooting
Endress+Hauser 157
Diagnostic information Remedy instructions Influenced measured
variables
No. Short text
442 Frequency output 1. Check process
2. Check frequency output settings
Measured variable status [from the factory]
1)
Quality Good
Quality substatus Ok
Coding (hex) 0x80 to 0x83
Status signal S
Diagnostic behavior Warning
1) Diagnostic behavior can be changed. This causes the overall status of the measured variable to change.
Diagnostic information Remedy instructions Influenced measured
variables
No. Short text
442 Frequency output 1. Check process
2. Check frequency output settings
Measured variable status
Quality Good
Quality substatus Ok
Coding (hex) 0x80 to 0x83
Status signal S
Diagnostic behavior Warning
Diagnostic information Remedy instructions Influenced measured
variables
No. Short text
443 Pulse output 1. Check process
2. Check pulse output settings
Measured variable status [from the factory]
1)
Quality Good
Quality substatus Ok
Coding (hex) 0x80 to 0x83
Status signal S
Diagnostic behavior Warning
1) Diagnostic behavior can be changed. This causes the overall status of the measured variable to change.
Diagnostic information Remedy instructions Influenced measured
variables
No. Short text
443 Pulse output 1. Check process
2. Check pulse output settings
Measured variable status
Quality Good
Quality substatus Ok
Coding (hex) 0x80 to 0x83
Status signal S
Diagnostic behavior Warning