Proline Prowirl F 200 PROFIBUS PA Commissioning
Endress+Hauser 77
Parameter Prerequisite Description Selection / User
entry
Factory setting
Select liquid type The following conditions are
met:
Order code for "Sensor
version", option "Mass flow"
The Liquid option is
selected in the Select
medium parameter.
Select measured liquid type. Water
LPG ((liquefied
petroleum gas))
User-specific liquid
Water
Fixed process pressure The following conditions are
met:
Order code for "Sensor
version", option "Mass flow
(integrated temperature
measurement)"
In the External value
parameter (→  102), the
Pressure option is not
selected.
Enter fixed value for process
pressure.
Dependency
The unit is taken from the
Pressure unit parameter
For detailed information
on the calculation of the
measured variables with
steam: →  186
For detailed information
on setting the parameter
in steam applications,
see the Special
Documentation for the
Wet Steam Detection
and Wet Steam
Measurement
→  212 application
package.
0 to 250 bar abs. 0 bar abs.
Enthalpy calculation The following conditions are
met:
Order code
"Sensor version", option
"Mass flow (integrated
temperature
measurement)"
"Application package",
option "Natural gas"
In the Select medium
parameter, the Gas option is
selected and in the Select
gas type parameter, the
Natural gas option is
selected.
Select the norm the enthalpy
calculation is based on.
AGA5
ISO 6976
AGA5
Density calculation The following conditions are
met:
In the Select medium
parameter, the Gas option is
selected.
In the Select gas type
parameter, the Natural gas
option is selected.
Select the norm the density
calculation is based on.
AGA Nx19
ISO 12213- 2
ISO 12213- 3
AGA Nx19
Enthalpy type The following conditions are
met:
In the Select gas type
parameter, the User-
specific gas option is
selected.
Or
In the Select liquid type
parameter, the User-
specific liquid option is
selected.
Define which kind of enthalpy
is used.
Heat
Calorific value
Heat