Proline Prowirl F 200 PROFIBUS PA Commissioning
Endress+Hauser 85
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
entry
Factory setting
Assign process variable – Select process variable for low
flow cut off.
• Off
• Volume flow
• Corrected volume
flow
• Mass flow
• Reynolds number
*
Off
On value low flow cutoff One of the following options is
selected in the Assign process
variable parameter (→  85):
• Volume flow
• Corrected volume flow
• Mass flow
• Reynolds number
*
Enter on value for low flow cut
off.
Positive floating-
point number
0
Off value low flow cutoff One of the following options is
selected in the Assign process
variable parameter (→  85):
• Volume flow
• Corrected volume flow
• Mass flow
• Reynolds number
*
Enter off value for low flow cut
off.
0 to 100.0 % 50 %
* Visibility depends on order options or device settings