Commissioning Proline Promag H 300 PROFINET
100 Endress+Hauser
Parameter Prerequisite Description Selection / User
interface / User
entry
Factory setting
Switch output function The Switch option is selected
in the Operating mode
parameter.
Select function for switch
output.
Off
On
Diagnostic
behavior
Limit
Flow direction
check
Status
Off
Assign diagnostic behavior In the Operating mode
parameter, the Switch
option is selected.
In the Switch output
function parameter, the
Diagnostic behavior option
is selected.
Select diagnostic behavior for
switch output.
Alarm
Alarm or warning
Warning
Alarm
Assign limit The Switch option is
selected in the Operating
mode parameter.
The Limit option is selected
in the Switch output
function parameter.
Select process variable for limit
function.
Off
Volume flow
Mass flow
Corrected volume
flow
Flow velocity
Conductivity
*
Corrected
conductivity
*
Totalizer 1
Totalizer 2
Totalizer 3
Temperature
*
Electronic
temperature
Volume flow
Assign flow direction check The Switch option is
selected in the Operating
mode parameter.
The Flow direction check
option is selected in the
Switch output function
parameter.
Select process variable for flow
direction monitoring.
Off
Volume flow
Mass flow
Corrected volume
flow
Volume flow
Assign status The Switch option is
selected in the Operating
mode parameter.
The Status option is
selected in the Switch
output function parameter.
Select device status for switch
output.
Empty pipe
detection
Low flow cut off
Digital output 1
*
Digital output 2
*
Digital output 3
*
Empty pipe detection
Switch-on value The Switch option is
selected in the Operating
mode parameter.
The Limit option is selected
in the Switch output
function parameter.
Enter measured value for the
switch-on point.
Signed floating-point
number
Country-specific:
0 l/h
0 gal/min (us)
Switch-off value The Switch option is
selected in the Operating
mode parameter.
The Limit option is selected
in the Switch output
function parameter.
Enter measured value for the
switch-off point.
Signed floating-point
number
Country-specific:
0 l/h
0 gal/min (us)
Switch-on delay The Switch option is
selected in the Operating
mode parameter.
The Limit option is selected
in the Switch output
function parameter.
Define delay for the switch-on
of status output.
0.0 to 100.0 s 0.0 s