Commissioning Proline Promag H 300 PROFINET
102 Endress+Hauser
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
interface / User
entry
Factory setting
Relay output function – Select the function for the
relay output.
• Closed
• Open
• Diagnostic
behavior
• Limit
• Flow direction
check
• Digital Output
Closed
Terminal number – Shows the terminal numbers
used by the relay output
module.
• Not used
• 24-25 (I/O 2)
• 22-23 (I/O 3)
–
Assign flow direction check In the Relay output function
parameter, the Flow direction
check option is selected.
Select process variable for flow
direction monitoring.
• Off
• Volume flow
• Mass flow
• Corrected volume
flow
Volume flow
Assign limit The Limit option is selected in
the Relay output function
parameter.
Select process variable for limit
function.
• Off
• Volume flow
• Mass flow
• Corrected volume
flow
• Flow velocity
• Conductivity
*
• Corrected
conductivity
*
• Totalizer 1
• Totalizer 2
• Totalizer 3
• Temperature
*
• Electronic
temperature
Volume flow
Assign diagnostic behavior In the Relay output function
parameter, the Diagnostic
behavior option is selected.
Select diagnostic behavior for
switch output.
• Alarm
• Alarm or warning
• Warning
Alarm
Assign status In the Relay output function
parameter, the Digital Output
option is selected.
Select device status for switch
output.
• Partially filled pipe
detection
• Low flow cut off
• Profinet Slot 18
*
• Profinet Slot 19
*
• Profinet Slot 20
*
Partially filled pipe
detection
Switch-off value In the Relay output function
parameter, the Limit option is
selected.
Enter measured value for the
switch-off point.
Signed floating-point
number
Country-specific:
• 0 l/h
• 0 gal(us)/min
Switch-off delay In the Relay output function
parameter, the Limit option is
selected.
Define delay for the switch-off
of status output.
0.0 to 100.0 s 0.0 s
Switch-on value The Limit option is selected in
the Relay output function
parameter.
Enter measured value for the
switch-on point.
Signed floating-point
number
Country-specific:
• 0 l/h
• 0 gal(us)/min
Switch-on delay In the Relay output function
parameter, the Limit option is
selected.
Define delay for the switch-on
of status output.
0.0 to 100.0 s 0.0 s
Failure mode – Define output behavior in
alarm condition.
• Actual status
• Open
• Closed
Open