Proline Promag H 300 PROFINET Commissioning
Endress+Hauser 113
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
entry
Factory setting
Format display A local display is provided. Select how measured values
are shown on the display.
1 value, max. size
1 bargraph + 1
value
2 values
1 value large + 2
values
4 values
1 value, max. size
Value 1 display A local display is provided. Select the measured value that
is shown on the local display.
Volume flow
Mass flow
Corrected volume
flow
Flow velocity
Corrected
conductivity
*
Totalizer 1
Totalizer 2
Totalizer 3
Current output 1
*
Current output 2
*
Current output 3
*
Temperature
*
Electronic
temperature
Noise
*
Coil current shot
time
*
Reference
electrode potential
against PE
*
Coating measured
value
*
Test point 1
Test point 2
Test point 3
Volume flow
0% bargraph value 1 A local display is provided. Enter 0% value for bar graph
display.
Signed floating-point
number
Country-specific:
0 l/h
0 gal/min (us)
100% bargraph value 1 A local display is provided. Enter 100% value for bar
graph display.
Signed floating-point
number
Depends on country
and nominal
diameter
Decimal places 1 A measured value is specified
in the Value 1 display
parameter.
Select the number of decimal
places for the display value.
x
x.x
x.xx
x.xxx
x.xxxx
x.xx