Diagnostics and troubleshooting Proline Promag H 300 PROFINET
156 Endress+Hauser
Diagnostic information Remedy instructions Influenced measured
variables
No. Short text
271 Main electronic failure 1. Restart device
2. Change main electronic module
• Conductivity
• Corrected conductivity
• Measured values 1
• Measured values 2
• Measured values 3
• Density
• Electronic temperature
• Flow velocity
• Mass flow
• Coil current shot time
• Reference electrode
potential against PE
• Noise
• Reference density
• Corrected volume flow
• Temperature
• Status
• Volume flow
Measured variable status
Quality Bad
Quality substatus Maintenance alarm
Coding (hex) 0x24 to 0x27
Status signal F
Diagnostic behavior Alarm
Diagnostic information Remedy instructions Influenced measured
variables
No. Short text
272 Main electronic failure 1. Restart device
2. Contact service
• Conductivity
• Corrected conductivity
• Measured values 1
• Measured values 2
• Measured values 3
• Density
• Electronic temperature
• Flow velocity
• Mass flow
• Coil current shot time
• Reference electrode
potential against PE
• Noise
• Reference density
• Corrected volume flow
• Temperature
• Status
• Volume flow
Measured variable status
Quality Bad
Quality substatus Maintenance alarm
Coding (hex) 0x24 to 0x27
Status signal F
Diagnostic behavior Alarm
Diagnostic information Remedy instructions Influenced measured
variables
No. Short text
273 Main electronic failure Change electronic • Conductivity
• Corrected conductivity
• Measured values 1
• Measured values 2
• Measured values 3
• Density
• Electronic temperature
• Flow velocity
• Mass flow
• Coil current shot time
• Reference electrode
potential against PE
• Noise
• Reference density
• Corrected volume flow
• Temperature
• Status
• Volume flow
Measured variable status
Quality Bad
Quality substatus Maintenance alarm
Coding (hex) 0x24 to 0x27
Status signal F
Diagnostic behavior Alarm