Proline Promag H 300 PROFINET Diagnostics and troubleshooting
Endress+Hauser 169
Diagnostic information Remedy instructions Influenced measured
variables
No. Short text
494 Switch output simulation 1 to n Deactivate simulation switch output
Measured variable status
Quality Good
Quality substatus Ok
Coding (hex) 0x80 to 0x83
Status signal C
Diagnostic behavior Warning
Diagnostic information Remedy instructions Influenced measured
variables
No. Short text
495 Diagnostic event simulation Deactivate simulation
Measured variable status
Quality Good
Quality substatus Ok
Coding (hex) 0x80 to 0x83
Status signal C
Diagnostic behavior Warning
Diagnostic information Remedy instructions Influenced measured
variables
No. Short text
496 Status input simulation Deactivate simulation status input
Measured variable status
Quality Good
Quality substatus Ok
Coding (hex) 0x80 to 0x83
Status signal C
Diagnostic behavior Warning
Diagnostic information Remedy instructions Influenced measured
variables
No. Short text
511 ISEM settings faulty 1. Check measuring period and integration
time
2. Check sensor properties
Conductivity
Corrected conductivity
Density
Electronic temperature
Flow velocity
Mass flow
Coil current shot time
Reference electrode
potential against PE
Noise
Reference density
Corrected volume flow
Temperature
Status
Volume flow
Measured variable status
Quality Bad
Quality substatus Maintenance alarm
Coding (hex) 0x24 to 0x27
Status signal C
Diagnostic behavior Alarm