Multi-Function Control ETMFC610 http://www.entecene.co.kr
Power
Function..................................................................... DISABLE/ENABLE
Function Block Time After Close ............................. 0.02 to 300.00sec in steps of 0.01 sec
Forward Power 1,2
Pickup Level ………………………………….OFF, 0.00 to 300.00MW in steps of 0.01MW
Time Delay……………………………………0.00 to 600.00sec in steps of 0.01sec
Polarizing Power………………………………3-Phase Active Power
Directional Power 1,2
Active Minimum Power Level..………………. OFF, -300.00 to 300.00 in steps of 0.01MW
Angle………………………………………….0.00 to 359.99° in steps 0.01°
Time Delay……………………………………0.00 to 600.00sec in steps of 0.01sec
Polarizing Power………………………………3-Phase Active Power and Reactive Power
Level Accuracy .......................................................... 5%
Timing Accuracy ....................................................... Max. 50㎳ at 0㎳ trip time delay
5% of trip time or ± 20㎳
Demand
Function..................................................................... DISABLE/ENABLE
Pickup Level
Phase/Ground/Neg Seq’ Current…..…………10A to 1600A in steps of 1A
Active Power………………………………….0.01 to 300.00 MW in step of 0.01 MW
Reactive Power………………………………..0.01 to 300.00 Mvar in step of 0.01 Mvar
Time Delay ................................................................ 0.00 to 600.00s in steps of 0.01s
Demand Type ............................................................ THERMAL/BLOCK
Thermal Interval Time .............................................. 5/10/15/20/30/60 min
Block Interval Time .................................................. 5/10/15/20/30/60 min
Level Accuracy .......................................................... ± 5%
Timing Accuracy ....................................................... Max. 50㎳ at 0㎳ trip time delay
5% of trip time or ± 20㎳