Multi-Function Control ETMFC610 http://www.entecene.co.kr
GLOBAL SETTING / GENERAL / MONITORING / OPERATION COUNT / Reset Count
Range
0 ~ 10000
Default
0
Step
1
It is to set the same operation number of switch. Set value is available
after operation count is reset. Count reset refers to “MAIN MENU/
MAINENANCE/ DATA RESET/ OPERATION COUNT or COUNT
ALL” menu.
NOTE :
1. When entering “MENU/ MAINENANCE/ DATA RESET”
menu to reset operation count, password 3 authentication is
required
2. The current operation count can be checked in the “MENU/
MAINENANCE/ COUNT/ ETMFC610” menu.
7.1.3.3. Contact Wear
Place the curser on “CONTACT WEAR” in MONITORING menu, press [ENT] button to move
into this menu. Switch contact wear and monitoring elements are set in this menu.
GLOBAL SETTING / GENERAL / MONITORING / CONTACT WEAR / Function
Range
DISABLE, ENABLE
Default
DISABLE
Step
~
Select whether to use switch (or CB) contact wear monitoring.
GLOBAL SETTING / GENERAL / MONITORING / CONTACT WEAR / Pickup (%)
Range
0.0 ~ 50.0 %
Default
20.0
Step
0.1 %
Set a pickup value to alarm when switch (or CB) contact wear reaches
set value.
>Function: DISABLE
>Alarm Count: 10000
>Reset Count: 0
[0~10000:1]
>Function: DISABLE
Alarm Pickup: 20.0
Time Delay: 0.01
Interrupt I1: 1.00
Interrpt Ct1: 10000
[DISABLE/ENABLE]
>Function: DISABLE
>Alarm Pickup: 20.0
Time Delay: 0.01
Interrupt I1: 1.00
Interrpt Ct1: 10000
[0.0~50.0:0.1%]