EasyManua.ls Logo

Entec ETMFC610 - Page 88

Default Icon
372 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Multi-Function Control ETMFC610 http://www.entecene.co.kr
78
EN
HANCED
TEC
HNOLOGY
GLOBAL SETTING / GENERAL / MONITORING / OPERATION COUNT / Reset Count
Range
0 ~ 10000
Default
0
Step
1
It is to set the same operation number of switch. Set value is available
after operation count is reset. Count reset refers to “MAIN MENU/
MAINENANCE/ DATA RESET/ OPERATION COUNT or COUNT
ALL” menu.
NOTE :
1. When entering “MENU/ MAINENANCE/ DATA RESET”
menu to reset operation count, password 3 authentication is
required
2. The current operation count can be checked in the “MENU/
MAINENANCE/ COUNT/ ETMFC610” menu.
7.1.3.3. Contact Wear
Place the curser on “CONTACT WEAR” in MONITORING menu, press [ENT] button to move
into this menu. Switch contact wear and monitoring elements are set in this menu.
GLOBAL SETTING / GENERAL / MONITORING / CONTACT WEAR / Function
Range
DISABLE, ENABLE
Default
DISABLE
Step
~
Select whether to use switch (or CB) contact wear monitoring.
GLOBAL SETTING / GENERAL / MONITORING / CONTACT WEAR / Pickup (%)
Range
0.0 ~ 50.0 %
Default
20.0
Step
0.1 %
Set a pickup value to alarm when switch (or CB) contact wear reaches
set value.
[OPERATION COUNT]
>Function: DISABLE
>Alarm Count: 10000
>Reset Count: 0
[0~10000:1]
[CONTACT WEAR]
>Function: DISABLE
Alarm Pickup: 20.0
Time Delay: 0.01
Interrupt I1: 1.00
Interrpt Ct1: 10000
[DISABLE/ENABLE]
[CONTACT WEAR]
>Function: DISABLE
>Alarm Pickup: 20.0
Time Delay: 0.01
Interrupt I1: 1.00
Interrpt Ct1: 10000
[0.0~50.0:0.1%]