EasyManua.ls Logo

Entec EVRC2A-N6-NT - Page 239

Default Icon
306 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
229
ENHANCED
TECHNOLOGY
10.1.5. Power
The following values are contained in the power metering.
y Real power(MW)
y Reactive power(Mvar)
y Apparent power(MVA)
y Power factor(%)
You can confirm in “MAIN NEMU / METERING / POWER”
MAIN MENU / METERING / POWER
[REAL POWER (MW)]
Pa: 0.00
Pb: 0.00 P3: 0.00
Pc: 0.00
[REACTIVE POW(MVAR)]
Pa: 0.00
Pb: 0.00 P3: 0.00
Pc: 0.00
[APPARENT POW(MWA)]
Pa: 0.00
Pb: 0.00 P3: 0.00
Pc: 0.00
[POWER FACTOR]
Pa: 0.0
Pb: 0.0 P3: 0.0
Pc: 0.0
Display measured values of power and power factor per phase. Use [] [] button to check
metering information of power.
10.1.6. Energy
The following values are contained in the energy metering.
y Positive watthour(MWh) & start date (Year/Month/Date Hour:Minute,Second)
y Negative watthour(MWh) & start date (Year/Month/Date Hour:Minute,Second)
y Positive varhour(Mvar) & start date (Year/Month/Date Hour:Minute,Second)
y negative varhour(Mvar) & start date (Year/Month/Date Hour:Minute,Second)
The updated rate of the energy meters is based on the “Time Constant” setting “MAIN MENU /
SETTING / MONITORING / DEMAND” The meters will update every 1/15 of the Demand
Constant. For example : if the Demand Constant is set to 15 minutes, the energy meters will
update every 1 minute (15min × 1/15 = 1 min)
The watt-hour and VAR-hour meters can be reset to 0 through “PRIMARY SETTING / RELAY
SETUP / CLEAR SAVED DATA / ENERGY”. The “SD(start date)” on LCD indicates the
time when the watt-hour and VAR-hour meters are reset.

Table of Contents