RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
69
ENHANCED
TECHNOLOGY
Connect Parameter
Move to “PRIMARY, ALTERNATE or EDITBANK SETTING / RELAY SETUP /
COMMUNICATION / DIALUP MODEM-1 or DIALUP MODEM-2 / CONNECT PARAM’”.
COMMUNICATION/ DIALUP MODEM / CONNET PARAM’ / Cmd Res’ TO
Range
0 ~ 255 sec
Default
2
Step
1 sec
Setting the Command response waiting time.
If there is no response from a modem during setting time, it is
considered as a communication failure after the setting time and the
status of modem failure is maintained.
COMMUNICATION/ DIALUP MODEM / CONNET PARAM’ / Connect TO
Range
0 ~ 255 sec
Default
30
Step
1 sec
Setting the Modem connection waiting time.
If there is no connection during setting time, it is considered as a
connection failure after the setting time, the status of modem failure is
maintained.
COMMUNICATION/ DIALUP MODEM / CONNET PARAM’ / Idle Time
Range
0 ~ 255 sec
Default
60sec
Step
1 sec
Setting the Modem connection close time.
During setting time, the connection is closed after the setting time.
COMMUNICATION/ DIALUP MODEM / CONNET PARAM’ / SMS Use (Option)
Range
DIABLE,ENABLE
Default
DIABLE
Step
~
Enable or disable Short Message Service (SMS) function.
COMMUNICATION/ DIALUP MODEM / CONNET PARAM’ / SMS Time (Option)
Range
0~255sec
Default
5sec
Step
1sec
SMS Time is a waiting time to wait for response after a short message
of SMS is sent.
[CONNECT PARAMETER]
>Idle Time: 60
>SMS Use: DIABLE
>SMS Time: 5
[CONNECT PARAMETER]
>Idle Time: 60
>SMS Use?: DIABLE
>SMS Time: 5
[CONNECT PARAMETER]
>Cmd Res’ TO: 2
>Connect TO: 30
>Idle Time: 60
[CONNECT PARAMETER]
>Cmd Res’ TO: 2
>Connect TO: 30
>Idle Time: 60
[CONNECT PARAMETER]
>Cmd Res’ TO: 2
>Connect TO: 30
>Idle Time: 60

Table of Contents