RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
74
ENHANCED
TECHNOLOGY
COMMUNICATION/ EVENT&ETC/ Daily Max I
Range
NO,YES
Default
NO
Step
~
Select whether to transfer the AI event about daily max. load current.
NO : Daily Max. Load Current is not recorded as event.
YES : Daily Max. Load Current is recorded as event.
NOTE :
This setting is supported from version 6.12 of
EVRC2A_N6,NT.
COMMUNICATION/ EVENT&ETC/ Daily Energy
Range
NO,YES
Default
NO
Step
~
Select whether to transfer the AI event about energy at midnight.
NO : Daily Energy is not recorded as event.
YES : Daily Energy is recorded as event.
NOTE :
This setting is supported from version 6.12 of
EVRC2A_N6,NT.
COMMUNICATION/ EVENT&ETC/ Time Syn’ Ref
Range
LOCAL,GMT
Default
LOCAL
Step
~
Set Reference Time Type. It signifies the time data type when Time
Synching with the master station.
NOTE :
This setting is set to be GMT and the setting values associated
with GMT(in “TIME SET&DIS TYPE” menu) are set up
incorrectly, the time internal clock in EVRC2A can be changed
incorrectly at time synchronization.
NOTE :
This setting is supported from version 7.04 of
EVRC2A_NT.
[EVENT&ETC]
>Daily Energy: NO
>Tims Syn’ Ref:LOCAL
>Evt Time Type:LOCAL
[EVENT&ETC]
> AI ‘P’ Unit: 10K
> Daily Max I: NO
> Daily Energy: NO
[EVENT&ETC]
> AI ‘P’ Unit: 10K
> Daily Max I: NO
> Daily Energy: NO