Underwriters Laboratories (UL) Agency Listings, Approvals, and Requirements
FCP-300/FCP-300ECS Manual — P/N LS10145-002FK-E:A 3/12/2021 15
Y = YES, N = NO, O = OPTIONAL
1. When configured for the Emergency Relocation and the Evacuation Equipment, the System must meet the Local
configuration Model FCP-300) with a minimum of one amplifier (Model FIK-50W/FIK-125W or FIK-INT50W) .
Model/Module Description Local Releasing
Remote
Station
Auxiliary
Central
Station
Emergency
Signaling
Table 2.1 NFPA Requirements for the FCP-300 (Continued)
Model/Module Description CS Local Auxiliary
Remote
Station
EVAC
5
Mass Notification
(In-Building)
5
FIK-50W
50W Amp
1
OOO O Y YO
FIK-50WHV
50W Amp
1
OOO O Y Y
FIK-125W
125W amp
1
OOO O Y Y
FIK-125WHV
125W Amp
1
OOO O Y Y
FIK-INT50W
Internal 50W
1
Amp
OOO O Y Y
FIK-SW24 Switch annunciator O O O O O Y
FIK-CE4
Speaker expander mod
3
OOO O O O
FIK-6815 SLC Expander O O O O O O
FIK-NVCM Network Voice Card O O O O O O
FIK-NIC Network Card O O O O O O
FIK-FML / FIK-FSL Fiber Module O O O O O O
Y = YES, N = NO, O = OPTIONAL
1. A maximum of eight 50/125 Watts Amplifiers for a maximum of 1000 Watts per the Fike Series, ECS System.
2. A maximum of one Voice Control Module per the Fike Series, ECS System.
3. A maximum of one Speaker Expander Module per Model FIK-50W/FIK-125W.
4. A maximum of two Remote Microphone modules per the Fike Series, ECS System.
5. When the System is configured for the emergency relocation and evacuation equipment, the System must comply with the
Local configuration (i.e., Model FCP-300) with a minimum of one amplifier (i.e., Models: FIK-50W/FIK-125W, or
FIK-INT50W).
Table 2.2 NFPA Requirements for FCP-300ECS