92 FCP-300/FCP-300ECS Manual — P/N LS10145-002FK-E:A 3/12/2021
Section 9: Programming
This Section of the Manual describes how to manually program the control panel from the built-in annunciator. Each subsection
describes these Menu options in detail. All options described in this Section can be performed using the HFSS Programming Tool.
9.1 UL 864 / UL 2572 Programming Requirements
9.2 Modules
This Section lists the options available under the Module Option in the Program Menu. The following modules are available for the con-
trol panel:
9.2.1 Edit Modules
The features that can be edited when this option is selected are, module name, and Class of wiring (Class A or Class B).
To edit an existing module, follow these steps:
1. Enter the Installer Code.
2. Select 7 for the Program Menu.
3. Press 1 to enter the Module Menu.
4. Press 1 to edit a module.
5. Use the up or down arrow to select the module you want to edit. Then press ENTER.
Editing Module ID
6. Press the up or down arrow key to modify the Module ID.
Naming Modules
You can assign an English name to a System hardware module to make it easier to recognize on a display.
IMPORTANT!
Before any customized programming is done, the JumpStart should be run first. After the JumpStart is run, thoroughly test the System.
The reason the System should be tested after the JumpStart is run is due to the fact that the JumpStart automatically programs the
System, searching for and configuring all SLC and SBUS devices it locates. The JumpStart allows you to confirm the integrity of the
installation prior to performing any custom programming. After you determine the hardware is properly installed, you can perform the
custom programming.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES:
This product incorporates field programmable software. In order for the product to comply with the requirements in the Standard for
Control Units and Accessories for Fire Alarm Systems, UL 864 and UL 2572, certain programming features or options must be limited
to specific values or not used at all as indicated below.
Programming
Option
Menu Item
Permitted in
UL 864
(Y/N)
Permitted in
UL 2572
(Y/N)
Possible Settings
Settings
Permitted in
UL 864
Settings
Permitted in
UL 2572
Time Options Auto-resound Yes Yes 4 hrs, 24hrs 4 hours if using
SWIFT devices
4 hours if using
SWIFT devices
Time Options Low AC Report Delay Yes Yes 0–30 hours 1–3 1–3
Display Oldest Event Y (Enabled) Yes Yes Yes & No Yes Yes
N (Disabled) No No Yes & No No No
Initial Delay 0-28 Yes Yes 0-28 3 3
Inter Message Delay 4-32 No No 4-32 4-32 4-28
Alarm Verification Alarm Verification Yes Yes 60-250
(Confirmation period)
60 60
Auto Reset
ECS MIC Triggered
Event
Auto Reset ECS MIC
Triggered Event
Yes Yes Never Timer Event
Disabled
Never Timer Event
Disabled
Never Timer
Event Disabled
ECS Input ECS Input Yes Yes Latching
Non-Latching
Latching Latching
Event Priority CO Alarm No No Yes & No No No
Table 9.1 UL 854/UL 2572 Programming Requirements
FIK-RA100 FIK-50W FIK-5496 NAC Expander
FIK-RA1000 FIK-125W FIK-RPS1000 intelligent power module
FIK-RA2000 LCD annunciators FIK-5880 LED I/O module FIK-INT50W or FIK-DUAL50W watt audio amplifier
FIK-NIC network interface card FIK-5865 LED annunciator
FIK-6815 SLC Loop Expander for Fike devices FIK-NVCM network voice control module
FIK-5824 serial/parallel printer interface module FIK-RVM remote voice module
NOTE: If you are working on a networked System, you will need to select which panel you want to program.
NOTE: For the Internal devices, FIK-NIC and FIK-NVCM, you cannot edit their module ID.