EasyManua.ls Logo

Fike FCP-300 - FIK-6815 Connection to the Panel; FIK-5824 Serial;Parallel Interface Module Installation

Fike FCP-300
175 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FIK-5824 Serial/Parallel Interface Module Installation Control Panel Installation
FCP-300/FCP-300ECS Manual — P/N LS10145-002FK-E:A 3/12/2021 39
7. Select a name, if desired (See “Naming Modules” on page 121.).
You are now ready to connect SLC devices to the FIK-6815. Figure 4.27 is a drawing of the FIK-6815 board, showing the
location of terminals and DIP switches.
Figure 4.27 FIK-6815 Board
4.8.1 FIK-6815 Connection to the Panel
Connect the FIK-6815 to the control panel as shown in Figure 4.28. After the FIK-6815 is connected to the panel, it must be
added to the System. The programming steps are described in Section 9.2.2.
Figure 4.28 FIK-6815 Connection to Main Panel Assembly
4.9 FIK-5824 Serial/Parallel Interface Module Installation
The FIK-5824 Serial/Parallel Printer Interface Module allows you to connect a printer to the panel, so you can print a real-time
log of the System Events. The procedure to install the FIK-5824 appear below.
The FIK-5824 and the printer connected to the FIK-5824 Parallel port is ancillary, the serial port can be used for the primary
fire signaling. The printer must be a UL 864 listed printer.
To install the FIK-5824, do the following:
1. Make sure the power is off at the panel.
2. Connect the FIK-5824 to the panel as shown in Figure 4.29.
To panel via SBUS
To SLC loop
Supervised
Power-Limited

Table of Contents

Other manuals for Fike FCP-300

Related product manuals