160 FCP-300/FCP-300ECS Manual — P/N LS10145-002FK-E:A 3/12/2021
Compatible Devices Four-Wire Smoke Detectors/Devices (UL Listed)
System Sensor 2112/24AITR Photoelectric 0.50 60/70
System Sensor 2112/24/D Photoelectric 0.05 50
System Sensor 2112/24R Photoelectric 0.50 60/70
System Sensor 2112/24TR Photoelectric 0.50 60/70
System Sensor 2112/24T/D Photoelectric w/135° Thermal 0.05 50
System Sensor 2112/24TSRB Photoelectric w/135° Thermal Supervisory
Relay
15 45
System Sensor 2312/24TB Photoelectric 0.12 50
System Sensor 2412 (12 volt) Photoelectric 0.12 77
System Sensor 2412AT (12 volt) Photoelectric 0.12 58
System Sensor 2412TH (12 volt) Photoelectric 0.12 77
System Sensor 2424 Photoelectric 0.10 41
System Sensor 2424TH Photoelectric 0.10 41
System Sensor 2451 Photoelectric 0.10 39
System Sensor 2451TH (with/B402B Base) Photoelectric 0.10 39
System Sensor 2W-MOD Loop Test/Maintenance Mod. 30 50
System Sensor 4W-B (12/24 Volt)
Photoelectric I
3
.05 23
System Sensor4WT-B (12/24 Volt)
Photoelectric I
3
w/Therm
.05 23
System Sensor 4WTA-B (12/24 Volt) I
3
Photo w/ Therm Sounder .05 35
System Sensor 4WTR-B (12/24 Volt)
I
3
Photo w/ Therm/Relay
.05 35
System Sensor 4WTAR-B (12/24 Volt)
I
3
Photo w/ Therm/Sounder/Relay
.05 50
System Sensor 4WITAR-B (12/24 Volt)
I
3
Photo w/ Isolated Therm/Sounder/Relay
.05 50
System Sensor 2W-MOD2
I
3
Loop Test/Maintenance Mod.
.05 *
System Sensor RRS-MOD
I
3
Reversing Relay/Sync Module
.05 *
System Sensor 6424 Projected Beam 10 28.4
System Sensor Beam 1224(S) Projected Beam 17 38.5
* Contact manufacturer for current draws
Smoke Detector/Base Detector Type
Max Standby
Current (mA)
Alarm Current
(mA)
Table A.2 Compatible Four-Wire Smoke Detectors