3.4 Programming Mode
3-40
Table 3.4-15 Running Status 3 (6_24) bit assignment
Bit
Symbol
Content
Bit
Symbol
Content
15
-
Always “0.”
7
FAN
“1” when the fan is in operation.
14
ID2
“1” when current 2 is detected.
6
KP
1 when keypad operation being
performed
13
IDL
“1” when low current is detected.
5
OL
“1” when a motor overload early
warning is issued.
12
ID
“1” when current is detected.
4
IPF
“1” during auto-restarting after
momentary power failure.
11
OLP
“1” under overload prevention
control.
3
SWM2
“1” when motor 2 is selected.
10
LIFE
“1” when a lifetime early warning is
issued.
2
RDY
“1” when the inverter is ready to
run.
9
OH
“1” when a heat sink overheat early
warning is issued.
1
FDT
“1” when frequency is detected.
8
TRY
“1” during auto-resetting.
0
FAR
“1” when a frequency arrival signal
is issued.

Table of Contents