3.4 Programming Mode
3-41
OPERATION USING THE KEYPAD
3.4.7 Copying data “Data Copying: 7.Cpy”
Data copying is used when reading function code data from the inverter and saving it in the TP-E2 keypad or in the
multifunction keypad (TP-A2SW), when writing function code data to another inverter, or when comparing function
code data saved to the keypad with function code data set in the inverter.
In addition, using menu number 7 allows you to store the running status information in the keypad, detach the
keypad from the inverter, connect it to a PC running FRENIC Loader at an office or off-site place, and check the
inverter running status without removing the inverter itself.
To store the inverter running status information in the keypad, use “Read data” (read) or “Read inverter running
information” (CHEC) function. For details on how to connect the keypad to a PC and check the inverter running
status information stored in the keypad, refer to the FRENIC Loader Instruction Manual.
Table 3.4-4 below shows the menu transition in menu number 7 “Data Copying.” The TP-E2 keypad can store
function code data for a single inverter.
Table 3.4-4 “Data Copying” status transition
If “err” or “diff” appears, refer to “■ If unable to copy”.
List of copying functions
F 05 is in
verification error