5.2 Function Code Tables
5-28
Function
code
Name
Control method and Data setting range
Change when running
Data copying
Factory
default
Related page
A49
(Notch filter resonance
frequency)
1 to 500 Hz
Y
Y
200
A50
(Notch filter attenuation level)
0 to 40 dB
Y
Y
0
A51
Cumulative run time of motor
2
0 to 99990 hours (Updated in 10 hour units)
Change in cumulative motor run time (Reset possible)
N
N
0
-
A52
Startup count for motor 2
0 to 65535 times
For adjustment when carrying out replacement
Y
N
0
A53
Motor 2 (%X correction factor
1)
0 to 300 %
Y
Y1Y2
100
A54
(%X correction factor 2)
0 to 300 %
Y
Y1Y2
100
A55
(Torque current under vector
control)
0.00 to 2000 A
N
Y1Y2
*6
A56
(Induced voltage factor under
vector control)
50 to 100 %
N
Y1Y2
*6
A57
(For adjustment by
manufacturer *9)
0.000 to 20.000 s
Y
Y1Y2
*6
A58
Speed control 2
(Notch filter width)
0 to 3 (0: Narrow to 3: Wide)
Y
Y
2
A60
Speed display coefficient 2
0.00 to 600.00
0.00: Use E50
Y
Y
0.00
A61
Constant rate of feeding
coefficient 2/
Speed display auxiliary
coefficient 2
0.000 to 9999
Y
Y
1.000
A62
Starting frequency 2
(Holding time)
0.00 to 10.00 s
Y
Y
0.00
A63
Stop frequency 2
0.0 to 60.0 Hz; 999 (Based on F25 setting)
Y
Y
999
A64
(Detection method)
0: Actual speed/estimated speed
1: Reference speed
100: Follow setting of F38
N
Y
100
A65
(Holding time)
0.00 to 10.00 s
Y
Y
0.00
A66
Motor 2
(Thermistor operation
selection)
0: Disable
1: PTC (OH4 trips and inverter stops)
2: PTC (Output signal (THM) is out, and motor continues to run)
3: NTC (OH4 trips and inverter stops)
100: G1 compatible operation
Y
Y
100
A67
(Operation level)
0.00 to 5.00 V
Y
Y
0.35
A98
(Function selection)
0 to 255
Bit 0: Current limiter (F43, F44) (0: Disable, 1: Enable)
Bit 1: Rotational direction control (H08) (0: Disable, 1: Enable)
Bit 2: Non-linear V/f (H50 to H53, H65, H66) (0: Disable, 1: Enable)
Bit 3: PID control (J01 to J62, H91) (0: Disable, 1: Enable)
Bit 4: Brake signal (0: Disable, 1: Enable)
Bit 5: Braking timer at startup (H195) (0: Disable, 1: Enable)
Bit 6 to 7: Reserved
N
Y
0
5-265
*6: Factory defaults are depended on motor capacity.
*9: This is a function code for adjustment by the manufacturer. Do not change.