5.3 Description of Function Codes 5.3.1 F codes (Fundamental functions)
5-67
FUNCTION CODES
Chap 5
FUNCTION
CODES
F Codes
E Codes
C Codes
P Codes
H Codes
A Codes
b Codes
r Codes
J Codes
d Codes
U Codes
y Codes
K Codes
F01
Frequency setting 1
Related function code:
F18 Bias (Frequency setting 1)
C30 Frequency setting 2
C31 to C35 Analog input adjustment (Terminal [12])
C36 to C40 Analog input adjustment (Terminal [C1] (C1 function))
C41 to C45 Analog input adjustment (Terminal [V2])
C55 to C56 Analog input adjustment (Terminal [12])
(Bias, Bias reference point)
C61 to C62 Analog input adjustment (Terminal [C1] (C1 function))
(Bias, Bias reference point)
C67 to C68 Analog input adjustment (Terminal [V2]]
(Bias, Bias reference point)
C74 to C78 Analog input adjustment (Terminal [C1] (V3 function))
C82 to C83 Analog input adjustment (Terminal [C1] (V3 function))
(Bias, Bias reference point)
C50 Bias (Frequency setting 1) (Bias reference point)
H61 UP/DOWN control - Initial value selection
d59, d61 to d63 Command (Pulse train input)
Select setting method of frequency setting. Select Frequency setting 1 with function code F01, and Frequency
setting 2 with C30. Frequency setting 1 and Frequency setting 2 are selected with “Frequency setting 2/Frequency
setting 1 “Hz2/ Hz1”” assigned to the digital input terminal. ( Function code E01 to E09 data = 11).
F01, C30 data
Command source
0
Frequency setting with keypad (refer to the following descriptions to find the setting method)
1
Setting with voltage value to be input for terminal [12] (0 to ±10 VDC, maximum output
frequency/±10 VDC)
2
Setting with current value (4 to 20 mA DC, maximum output frequency/20 mA DC) input for
terminal [C1] (C1 function)
(Set slide switch SW8 on the PCB to the [C1] side (factory default).
3
Setting with result of adding the voltage value to be input for terminal [12] (0 to ±10 VDC,
maximum output frequency/±10 VDC) and the current value to be input for terminal [C1] (4 to
20 mA DC, maximum output frequency/20 mA DC)
(If the result of addition is equal to or higher than the maximum output frequency, frequency is
restricted to the maximum output frequency.)
5
Setting with voltage value to be input for terminal [V2] (0 to ±10 VDC, maximum output
frequency/±10 VDC)
(Set slide switch SW5 on the PCB to the [V2] side (factory default)).
6
Setting with voltage value to be input for terminal [C1] (V3 function) (0 to ±10 VDC, maximum
output frequency/±10 VDC)
(Set slide switch SW8 on the PCB to the [V3] side).
7
Setting with UP command “UP” and DOWN command “DOWN” assigned to the digital input
terminal
It is necessary to assign the UP command (Data = 17) and DOWN command (Data = 18) to
digital input terminal [X1] to [X9]. (E01 to E09)
8
Frequency setting with keypad (with balanceless/bumpless function)
10
Setting with pattern operation
11
Frequency setting with digital input interface card (option)
(Refer to the Option Instruction Manual for details.)
12
Setting with pulse train input “PIN” (data = 48) assigned to digital input terminal [X6] and [X7],
or with PG interface card (option)
Note: If using terminal [X6] and [X7] with pulse train input, they may be affected by noise from
other wiring.
Keep wiring to terminal [X6] and [X7] and other wiring as far apart as possible.