5.3 Description of Function Codes 5.3.1 F codes (Fundamental functions)
Terminal [C1] (C1 function) range / polarity selection (C40)
Handling when bias value is set to minus
4 to 20 mA (factory default)
Limit below 0 point with 0
Enable below 0 point as minus value.
In order to use terminal [C1] with the C1 function and V3 function, the following settings are necessary.
When using C1 function
(4 to 20 mA)
C1 side
(factory default)
0 (unipolar)
(factory default)
10 (bipolar)
When using C1 function
(0 to 20 mA)
1 (unipolar)
11 (bipolar)
When using V3 function
(0 to ±10 V)
When using V3 function
(0 to +10 V)
Refer to “Chapter 2 2.2.7” for details on SW8.