5.3 Description of Function Codes 5.3.1 F codes (Fundamental functions)
5-69
FUNCTION CODES
Chap 5
FUNCTION
CODES
F Codes
E Codes
C Codes
P Codes
H Codes
A Codes
b Codes
r Codes
J Codes
d Codes
U Codes
y Codes
K Codes
[ 2 ] Setting the frequency with analog input (F01 = 1 to 3, 5, 6)
It is possible to arbitrarily specify a frequency setting from the analog inputs (voltage value to be input to terminal
[12], [V2], and [C1] (V3 function), or current value to be input to terminal [C1] (C1 function)) by multiplying them with
the gain and adding the bias. The polarity can be selected and the filter time constant and offset can be adjusted.
Table Adjustment constants of Frequency setting 1
F01 data
Input terminal
Input range
Bias
Gain
Polarity
selection
Filter
Offset
Bias
Base
point
Gain
Base
point
1
[12]
0 to +10 V,
-10 to +10 V
F18
C50
C32
C34
C35
C33
C31
2
[C1] (C1 function)
4 to 20 mA
0 to 20 mA
F18
C50
C37
C39
C40
C38
C36
3
[12] + [C1]
(C1 function)
(Set by result of
addition)
0 to +10 V,
-10 to +10 V
F18
C50
C32
C34
C35
C33
C31
4 to 20 mA
0 to 20 mA
F18
C50
C37
C39
C40
C38
C36
5
[V2]
0 to +10 V,
-10 to +10 V
F18
C50
C42
C44
C45
C43
C41
6
[C1] (V3 function)
0 to +10 V,
-10 to +10 V
F18
C50
C75
C77
C78
C76
C74
Table Adjustment constants of Frequency setting 2
C30
data
Input terminal
Input range
Bias
Gain
Polarity
selection
Filter
Offset
Bias
Base
point
Gain
Base
point
1
[12]
0 to +10 V,
-10 to +10 V
C55
C56
C32
C34
C35
C33
C31
2
[C1] (C1 function)
4 to 20 mA
0 to 20 mA
C61
C62
C37
C39
C40
C38
C36
3
[12] + [C1]
(C1 function)
(Set by result of
addition)
0 to +10 V,
-10 to +10 V
C55
C56
C32
C34
C35
C33
C31
4 to 20 mA
0 to 20 mA
C61
C62
C37
C39
C40
C38
C36
5
[V2]
0 to +10 V
C67
C68
C42
C44
C45
C43
C41
6
[C1] (V3 function)
0 to +10 V,
-10 to +10 V
C82
C83
C75
C77
C78
C76
C74
Offsets (C31, C36, C41, C74)
C31, C36, C41 or C74 configures an offset for an analog voltage/current input. The offset also applies to signals
sent from the external equipment.
Filters (C33, C38, C43, C76)
C33, C38, C43 and C76 provide the filter time constants for the voltage and current of the analog input. The larger
the time constant, the slower the response. Specify the proper filter time constant taking into account the response
speed of the machine (load). If the input voltage fluctuates due to line noises, increase the time constant.
Polarity selection for terminal (C35, C45, C78)
C35, C45 and C78 configures the polarity and therefore the input range for analog input voltage.
C35, C45, C78 data
Terminal [12], [V2], [C1] (V3 function) input specifications
0: Bipolar
-10 to +10 V (factory default)
1: Unipolar
0 to +10 V (Negative value of voltage is regarded as 0 V)