5.3 Description of Function Codes 5.3.1 F codes (Fundamental functions)
5-75
FUNCTION CODES
Chap 5
FUNCTION
CODES
F Codes
E Codes
C Codes
P Codes
H Codes
A Codes
b Codes
r Codes
J Codes
d Codes
U Codes
y Codes
K Codes
When operating unipolar analog input as bipolar
(terminal [12] (C35 = 0), terminal [V2] (C45 = 0), terminal [C1] (C1 function) (C40 = 10, 11), terminal [C1] (V3
function) (C78 = 0))
By setting the bias value to a minus value, it is possible to obtain a negative reference frequency.
Example of frequency setting with terminal [V2] when -100 % is set to the bias value is shown in the diagram below.
F18 = -100.0%
10 V
0 V
5 V
Reference frequency
Reference frequency
-100%
Reference frequency
+100 %
Reference frequency
0%
(V2) input