5.3 Description of Function Codes 5.3.1 F codes (Fundamental functions)
Table When P99 = 1 or 3 (motor characteristic 1, 3)
Thermal time
constant τ
(factory default)
Thermal time
constant setting
Standard current
value Imax
Characteristics coefficient
switch frequency
Characteristics
coefficient
Continuous
allowance current
value x 150 %
When F10=2 is set, cooling effect by output frequency will not decrease, therefore, overload detection level
becomes constant value (F11) without decrease.
Table If P99 = 20, 21, 22, or 23 (permanent magnet synchronous motor)
Thermal time
constant τ
(Factory default)
Thermal time
constant setting
Standard current
value Imax
Characteristics coefficient
switch frequency
Characteristics
coefficient
Continuous
allowance current
value x 150 %
Operation level (F11)
F11 sets operation level of electronic thermal.
Normally, set the motor continuous allowance current (in general, about 1.0 to 1.1 times of motor rated current)
when operating at base frequency in ampere units.
For disabling electronic thermal as disable, set F11 = 0.00: Disable.