5.3 Description of Function Codes 5.3.1 F codes (Fundamental functions)
5-91
FUNCTION CODES
Chap 5
FUNCTION
CODES
F Codes
E Codes
C Codes
P Codes
H Codes
A Codes
b Codes
r Codes
J Codes
d Codes
U Codes
y Codes
K Codes
Thermal time constant (F12)
F12 sets thermal time constant of the motor. For overload detection level that is set by F11, set the electronic thermal
operation time when 150 % of current is flowing continuously. Thermal time constant of general-purpose motor of
Fuji Electric and general motors is 5 minutes for 22 kW or lower, and 10 minutes (factory default state) for 30kW or
higher.
Data setting range: 0.5 to 75.0 (min)
(Example) When the data of function code F12 is set to “5” (5 minutes).
As shown in the figure below, when 150 % of current of operation level that was set flows for 5 minutes, motor
overload (alarm 0l1) protection function will operate. In addition, with 120 %, it operates after 12.5 minutes.
The time when alarm actually occurs is shorter than the set data because the time until the current reaches 150 %
level after exceeding the continuous allowance current (100 %) is considered.
Fig. Example of current-operation time characteristics
Operation time (min.)
Changed
with F12
(Output current / Detection level current) x 100 (%)