5.3 Description of Function Codes 5.3.3 C codes (Control functions)
5-196
C30
Frequency setting 2 (Refer to F01)
For details on Frequency setting 2, refer to the description for function code F01.
C31 to C35
C36 to C40
C41 to C45
C74 to C78
Analog input adjustment (terminal [12])
(Offset, Gain, Filter, Gain reference point, Polarity selection)
Analog input adjustment (terminal [C1] C1 function)
(Offset, Gain, Filter, Gain reference point, range selection)
Analog input adjustment (terminal [V2])
(Offset, Gain, Filter, Gain reference point, Polarity selection)
Analog input adjustment (terminal [C1] V3 function)
(Offset, Gain, Filter, Gain reference point, Polarity selection)
Refer to F01 for details on frequency settings.
C55, C56
C61, C62
C67, C68
C82, C83
Bias (for PID, Frequency setting 2 (terminal [12]))
(Bias, Bias reference point) (Refer to F01)
Bias (for PID, Frequency setting 2 (terminal [C1]) (C1 function))
(Bias, Bias reference point)(Refer to F01)
Bias (for PID, Frequency setting 2 (terminal [V2])
(Bias, Bias reference point)(Refer to F01)
Bias (for PID, Frequency setting 2 (terminal [C1]) (V3 function))
(Bias, Bias reference point)(Refer to F01)
You can adjust the gain, bias, polarity, filter time constant and offset which are applied to analog inputs (voltage
inputs to terminals [12], [V2], and [C1] (V3 function) and current input to terminal [C1] (C1 function)).
Adjustable items for analog inputs (excluding those for frequency command 1)
Input
terminal
Input range
Bias
Gain
Polarity
Filter
Offset
Bias
Reference
point
Gain
Reference
point
[12]
0 to +10 V,
-10 to +10 V
C55
C56
C32
C34
C35
C33
C31
[C1] (C1)
4 to 20 mA,
0 to 20 mA
C61
C62
C37
C39
C40
C38
C36
[V2]
0 to +10 V,
-10 to +10 V
C67
C68
C42
C44
C45
C43
C41
[C1] (V3)
0 to +10 V,
-10 to +10 V
C82
C83
C75
C77
C78
C76
C74
Offsets (C31, C36, C41, C74)
C31, C36, C41 or C74 configures an offset for an analog voltage/current input. The offset also applies to signals
sent from the external equipment.
Data setting range: -5.0 to +5.0(%)
Filters (C33, C38, C43, C76)
C33, C38, C43 and C76 provide the filter time constants for the voltage and current of the analog input. The larger
the time constant, the slower the response. Specify the proper filter time constant taking into account the response
speed of the machine (load). If the input voltage fluctuates due to line noises, increase the time constant.
• Data setting range: 0.00 to 5.00 (s)