2.1 Installation
2-1
INSTALLATION AND WIRING
Chap 2
2.1 Installation
(1) Installation environment
Please install FRENIC-MEGA in locations which meet the requirements specified in Chapter 1 “1.3.1 Operating
environment”.
(2) Installation surface
Please install the inverter on noncombustibles such as metal. Also, do not mount it upside down or horizontally.
Install on noncombustibles such as metal.
Failure to observe this could result in fire.
(3) Surrounding space
Secure the surrounding space shown in Fig. 2.1-1 and Table 2.1-1. If
enclosing the product in a cabinet and so on, be sure to provide adequate
ventilation to the cabinet, as the ambient temperature may rise. Do not
contain it in small enclosures with low heat dissipation capacity.
Installation of multiple inverters
If installing two or more units inside the same equipment or cabinet, they
must be installed side by side as a rule. If vertical installation is
unavoidable, install partitions to prevent heat dissipation from inverters
below affecting those above.
With FRN0115G2S-2G / FRN0060G2-4G or lower, only in the case
of an ambient temperature of 40 °C (104°F) or below is it possible to
install inverters and converters closely together horizontally.
Table 2.1-1 Surrounding space (mm (inch))
Type of Inverter
A
B
C
FRN□□□□
G2S-2G
FRN□□□□
G2-4G
0003 to 0008
0002 to 0004
50
(1.97)
100
(3.9)
0
(0)
0011 to 0115
0006 to 0060
10
(0.39)
0146 to 0432
0075 to 0520
50
(1.97)
100
(3.9)
0650 to 1386
150
(5.9)
150
(5.9)
C: Space in front of inverter unit
Fig. 2.1-1 Installation direction