5.3 Description of Function Codes 5.3.8 J codes (Applied functions) 
 
 
PID control (PID output limiter upper limit, PID output limiter lower limit)
 
 
The upper and lower limiters can be specified to the PID output, exclusively used for PID control. The settings are 
ignored when PID cancel “Hz/PID” is enabled and the inverter is operated at the reference frequency previously 
specified.   
( Function codes E01 to E09 data = 20) 
  PID Control (Upper limit of PID process output) (J18) 
J18 specifies the upper limit of the PID processor output limiter in %. If the value of “999” is specified to J18, the 
setting of the frequency limiter (Upper) (F15) will serve as the upper limit. 
  PID Control (Lower limit of PID process output) (J19) 
J19 specifies the lower limit of the PID processor output limiter in %. If the value of “999” is specified to J19, the 
setting of the frequency limiter (Lower) (F16) will serve as the lower limit. 
 
Condensation prevention (Duty)
 
 
The motor temperature can be raised while the inverter is stopped to prevent condensation forming by supplying 
DC current for a fixed period of time.   
This function does not work when a synchronous motor is selected. 
  Enable conditions 
By turning on condensation prevention “DWP” while the inverter is stopped, the condensation prevention function 
is started.   
(Function codes E01 to E09, data = 39) 
  Condensation prevention (Duty) (J21) 
The current flowing to the motor is based on DC braking 1 (operation level) (F21), and duty control is performed 
based on the condensation prevention duty (J21) ratio corresponding to DC braking 1 (time) (F22). 
100×
T
(F22)(time)brake DC
(J21)duty  prevention oncondensatiDew  =
 
 
 
Fig. 5.3-33 Condensation prevention operation 
 
 
Switch to commercial power sequence (Refer to E01 to E09)
 
 
Refer to the function code E01 to E09 switch to commercial power built-in sequence “ISW50” and “ISW60” items 
for a detailed explanation of the switch to commercial power sequence setting. 
 
 
PID control (Low liquid level stop starting feedback deviation, Low liquid level stop 
startup delay time)
 
 
Refer to the J08 item.